Two circuits can share the same cable, the same nominal current and the same panel row, and still need different miniature circuit breakers. A lighting circuit draws a steady current for hours and almost nothing else; a motor circuit draws six to eight times its rated current every time it starts. The device that protects one will nuisance-trip on the other, and the mistake usually traces back to a single number on the label being read as if it described the whole device.
Rated current is only one of three numbers printed on an MCB. The other two — the instantaneous trip band and the short-circuit capacity — decide whether the device survives the load it is asked to protect. This article sets out how to choose the rating for the two load families that dominate small distribution boards, with the cable limits and ambient corrections that usually change the final answer.
The Three Numbers Behind One Rating
A miniature circuit breaker to IEC 60898-1 carries a rated current, a trip curve letter and a short-circuit capacity. Each answers a different question, and only the first is normally discussed.
| Notation | What it states | How it is exceeded |
|---|---|---|
| Dans — rated current | The current the device carries indefinitely at the reference ambient temperature (30 °C for IEC 60898-1) without tripping | By a sustained overload, which the thermal element clears on a time-current basis |
| Curve letter — B, C or D | The band of current at which the magnetic element trips instantly: 3–5 In, 5–10 In, 10–20 In respectively | By inrush events that sit inside the band — a start, a driver, a cold filament |
| Icn or Icu — short-circuit capacity | The fault current the device can interrupt and still be serviceable (Icn to IEC 60898-1) or the higher of its two industrial ratings (Icu to IEC 60947-2) | By a prospective fault current above the rating — a failure mode, not a trip |

Rating selection is therefore not one decision. The load sets a minimum for In, the cable sets a maximum for In, the inrush sets a minimum for the curve letter, and the prospective fault current at the board sets a minimum for the capacity. All four constraints have to be satisfied at once, and for lighting and motor loads they pull in different directions.
MCB Rating Selection for Lighting Circuits
Lighting is close to an ideal resistive load once it is running. Current is steady, power factor is near unity on modern drivers, and there is no starting sequence. The design current is simply the connected load divided by the nominal voltage, reduced by whatever demand factor the design applies to circuits that are not all energised together.
The trap is the first half-second. LED drivers and electronic ballasts present a capacitor that charges through the supply impedance when the circuit is energised. Peak current can be tens of times the running current for well under a millisecond, and because it is capacitive the peak is limited only by the wiring and the supply — not by the driver’s rating. A single driver is harmless. Forty of them on one breaker is not, because their inrush events overlap.
Three practical consequences follow:
- Do not sit the design current at the device rating. A circuit drawing 15.5 A on a 16 A device has no margin for the thermal element’s tolerance, and nothing left for a warm enclosure. Leave at least 10–20 % headroom on steady lighting loads.
- Check the driver data for a maximum per breaker. Many driver manufacturers publish the number of units one protective device can supply, based on measured inrush and the device’s magnetic band. That number, not the wattage, decides how many fittings go on a circuit.
- Split the circuit rather than raise the rating. Going from 16 A to 20 A to stop nuisance tripping usually breaches the cable’s Iz before it solves the inrush problem, and it raises the magnetic threshold only from 80–160 A to 100–200 A — a small gain for a real loss of cable protection.
Where lighting runs continuously — warehouse high-bay, signage, 24-hour process lighting — the circuit is often sized at 125 % of the continuous load so that the device is not asked to carry its full rating for the whole working day. That rule is explicit in the North American code (NEC 210.19 and 210.20) and appears in many specifications elsewhere; either way, it is the reason a 10 A lighting load often ends up on a 16 A device rather than a 13 A one.
MCB Rating Selection for Motor Circuits
A motor circuit is protected by two devices doing two different jobs, and confusing them is the most common cause of a motor starter that trips on every start.
The overload relay — a thermal relay, or the thermal element inside a motor protection circuit breaker — is set to the motor’s full-load current and clears sustained overloads. The MCB upstream provides short-circuit protection only. It does not need to be set at the motor current, and in most starters it deliberately is not, because its magnetic element has to ride through the starting current without tripping.
| Méthode de démarrage | Typical starting current | Duration the device must ride through | What this means for the curve |
|---|---|---|---|
| Direct-on-line (DOL) | 6–8 × motor full-load current | 0.5–10 s, depending on load inertia | Type C often fails; type D or a motor-rated device is the usual answer |
| Étoile-triangle | 2–2.5 × full-load current at the supply | Transition period plus run-up | Type C is normally adequate on the line device |
| Démarreur progressif | 2–4 × full-load current, ramped | Set ramp time | Type C adequate; check the ramp does not overlap the magnetic band |
| Variable speed drive | Close to 1 × full-load current | Not applicable | The drive limits current; the MCB only clears faults |
The arithmetic is unforgiving. A 7.5 kW motor at 400 V draws roughly 15.5 A at full load. Direct-on-line starting at 6.5 times that is about 100 A. A 20 A type C device has a magnetic band of 100–200 A, so the starting current sits exactly on the lower edge of the band — some units will hold, some will trip, and the difference between them is manufacturing tolerance rather than design. A 16 A type D device has a band of 160–320 A and holds comfortably.
Note what the type D device does not do: it provides no useful overload protection for a 15.5 A motor, because its thermal element is calibrated for 16 A and its magnetic element only moves at 160 A. The overload relay is doing the protecting, and the cable is protected against overload by that relay, not by the breaker. This division of labour is why motor circuits are usually built around a motor protection circuit breaker or a combination starter rather than a bare MCB — the arrangement is set out in which device protects the cable and which protects the motor.
The Cable Sets the Ceiling, Not the Load
Whatever the load asks for, the device rating has to satisfy the coordination rule in IEC 60364-4-43: the design current Ib must not exceed the device rating In, and In must not exceed the cable’s current-carrying capacity Iz. The device must also clear an overload before the cable is damaged, which is expressed as I2 ≤ 1.45 Iz.
In practice the lower bound comes from the load and the upper bound comes from the cable, and the gap between them is where the device is chosen.
| Copper conductor | Reference Iz, PVC 70 °C, two loaded conductors, clipped direct | Usual device | Utilisation courante |
|---|---|---|---|
| 1.5 mm² | 17.5 A | 10 A or 16 A | Lighting sub-circuits, small final circuits |
| 2.5 mm² | 24 A | 16 A or 20 A | Socket outlets, larger lighting groups |
| 4 mm² | 32 A | 25 A or 32 A | Small motor circuits, sub-mains |
| 6 mm² | 41 A | 32 A or 40 A | Motor circuits, distribution sub-mains |
These are reference values at 30 °C ambient with no grouping and no thermal insulation. Every one of those conditions is usually violated inside a real enclosure, which is why the next two sections matter more than the table itself.
Inrush Is Usually the Real Constraint
Three load families produce inrush, and they behave differently enough that the same device cannot be assumed to handle all of them.
- Tungsten filament. Cold resistance is roughly a tenth of hot resistance, so the first cycles draw about ten times running current. The event lasts a few milliseconds and a type B device with a 3–5 In band can still hold, which is why B curves remain common on resistive heating and older lighting.
- LED drivers and electronic ballasts. Capacitive charging, with peaks well above the tungsten case but shorter. The constraint is cumulative: the peak depends on how many drivers see the same supply impedance at the same instant, so the limit is a count per breaker, not a multiple of running current.
- Motors. Six to eight times current for a duration measured in seconds. This is the only one of the three where the inrush lasts long enough to heat the bimetal as well as challenge the magnetic element, and the only one where the duration depends on the mechanical load rather than on the electrical circuit.
A device selected on thermal considerations alone will hold all three at rated current and fail the third at start. That is why the curve letter is chosen from the load’s starting behaviour and the In is chosen from the load’s steady behaviour — two decisions, taken separately.
Grouping and Ambient Temperature Change the Answer
An MCB is calibrated in free air at 30 °C. A distribution board is a closed metal box with a row of devices producing heat, and the air around them is routinely 45–55 °C in summer. Two correction factors stack on top of the reference Iz.
For 70 °C PVC insulation, an ambient of 40 °C gives a factor of about 0.87 and 45 °C about 0.79. Grouping adds a second reduction: two circuits bunched together take roughly 0.80 of their individual capacity, three about 0.70. Apply both and a 2.5 mm² circuit that looked like 24 A becomes about 16.7 A.
That number is the one the device has to fit under. It is also the step most often skipped, because the cable table and the breaker label are both read at reference conditions while the installation is not at reference conditions. The same logic applied to larger frames is covered in why a 250 A breaker is not 250 A inside a hot enclosure.
Worked Example: One Lighting Circuit and One Motor Circuit
The two circuits below share a board, an ambient of 40 °C and a grouping factor of 0.80. The answers diverge because the loads diverge.
| Étape | Lighting circuit | Motor circuit |
|---|---|---|
| Load | 18 LED high-bay fittings, 150 W each, 230 V single phase | 7.5 kW, 400 V three phase, full-load current 15.5 A |
| Design current Ib | 2,700 W ÷ 230 V = 11.7 A | 15.5 A running; 100 A at direct-on-line start |
| Cable | 2.5 mm² PVC, reference Iz 24 A | 4 mm² PVC, reference Iz 32 A |
| Corrected Iz | 24 × 0.87 × 0.80 = 16.7 A | 32 × 0.87 × 0.80 = 22.3 A |
| Caractéristiques techniques de l'appareil | 16 A — above Ib, below corrected Iz | 16 A — the relay, not the breaker, protects against overload |
| Curve | Type C, magnetic band 80–160 A, above the driver inrush peak of the group | Type D, magnetic band 160–320 A, above the 100 A start |
| What decides it | The corrected cable capacity — the load alone would allow 20 A | The starting current — the cable alone would allow 20 A |
Both circuits end on a 16 A device, and neither was chosen for the same reason. The lighting device is capped by the cable after correction; the motor device is capped by the starting current and protected against overload by a separate relay. A schedule that lists only “16 A” for both has captured the answer and lost the reasoning, which is what causes the substitution on site when the electrician reaches for whatever is in the van.
A Short MCB Rating Selection Checklist
- Calculate Ib from the load, applying the demand factor for the circuit type.
- Read Iz from the cable table, then apply ambient and grouping correction — in that order, both factors.
- Choose In to sit between Ib and corrected Iz, leaving 10–20 % headroom on steady loads.
- Choose the curve from the inrush: B for resistive, C for mixed and moderate inductive, D for direct-on-line motors.
- Check the magnetic band against the actual starting current, not against the rated current.
- Confirm the short-circuit capacity against the prospective fault current at that point in the board.
- For motor circuits, confirm which device provides overload protection and that the cable is protected by it.
Foire aux questions
Is a 16 A MCB always correct for a 2.5 mm² circuit?
At reference conditions, yes — 16 A sits comfortably under a 24 A capacity. In a hot, fully populated board the corrected capacity can fall to about 17 A, and in a bundle of three circuits to about 13 A, at which point a 16 A device no longer protects the cable. The correction factors decide, not the table.
Can I use a type C MCB on a motor?
Sometimes. A type C device has a magnetic band of 5–10 In, so a 20 A unit starts to trip magnetically at 100 A — right at the starting current of a 7.5 kW direct-on-line motor. For star-delta and soft-started motors the starting current is low enough that type C is normally fine; for direct-on-line it is a coin toss and type D is the safer specification.
Why does my LED lighting circuit trip when it is switched on?
Driver inrush, almost always. The peak is capacitive, very short, and accumulates across every driver on the circuit. The fix is fewer fittings per breaker or a device with a higher magnetic threshold — not a bigger In, which raises the threshold only slightly while removing cable protection.
Does a higher kA rating change the current rating?
No. The kA figure describes the fault current the device can interrupt, and it has no bearing on the current it carries. A 10 kA device and a 6 kA device of the same In and curve behave identically on overload; they differ only in what happens during a short circuit. The comparison is set out in 6 kA versus 10 kA breaking capacity.
Should the MCB rating match the motor nameplate current?
No. Matching it guarantees a trip on every start. The breaker is the short-circuit device and is sized above the starting current; the overload relay is set to the nameplate current and does the protecting. Where one device has to do both jobs, it is a motor protection circuit breaker with an adjustable thermal range, not a standard MCB.
Where the Rating Comes From
Selection is a sequence of ceilings: the load sets the floor, the corrected cable capacity sets the ceiling, the starting current removes part of the range, and the fault level at the board fixes the capacity class. For lighting circuits the ceiling usually binds. For motor circuits the starting current usually does.
Our miniature circuit breaker range lists rated current, curve and breaking capacity for each frame, and the ordering data a specification has to pin down is set out in how to specify an MCB range. Where the circuit is a motor starter rather than a final circuit, the device split is covered in how to choose the right breaker for the application and in the B, C and D trip curves in detail.